Hoshizaki KM-2000SRF3 Manual de usuario Pagina 44

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 56
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 43
44
9. ADJUSTMENT OF WATER REGULATING VALVE - WATER-COOLED
MODEL ONLY
The Water Regulating Valve (also called “WATER REGULATOR”) is factory-adjusted. No
adjustment is required under normal use. Adjust the Water Regulator, if necessary, using the
following procedures.
1) Attach a pressure gauge to the high-side line of the system. Or prepare a thermometer to
check for the condenser drain temperature.
2) Rotate the adjustment screw by using a flat blade screwdriver, so that the pressure gauge
shows 270 PSIG or the thermometer reads 104–115° F, 5 minutes after a freeze cycle or
icemaking process starts. When the pressure exceeds 270 PSIG, or the condenser drain
temperature exceeds 115° F, rotate the adjustment screw counterclockwise. See Fig. 1.
3) Check that the pressure or the condenser drain temperature holds a stable setting.
Fig. 1
Vista de pagina 43
1 2 ... 39 40 41 42 43 44 45 46 47 48 49 ... 55 56

Comentarios a estos manuales

Sin comentarios